(1) measurement of the stator, winding between each phase and winding to ground insulation resistance.
Insulation resistance R should meet the following formula.
R>Un/(1000+P/1000)(MΩ)
Un: rated voltage of motor winding (V)
P: motor power (KW)
For the motor with Un = 380V, R>0.38MΩ.
If the insulation resistance is low, it can be.
a: no-load operation of the electric motor for 2 to 3h drying.
b: using 10% of the rated voltage of low-voltage alternating current into the winding or three phase winding in series with DC baking, keeping the current at 50% of the rated current.
c: use the fan to send in hot air or heating element heating.
(2) Clean the electric motor.
(3) Replace the bearing grease.